Connecting an S7/200 to TOP Server over Ethernet

I am having trouble making the connection to the S7-200 Ethernet?  What should the TSAP settings be?

The directions for setting the TSAP are in the S7-200 Ethernet TOP Server Help menu. To locate the topic, please use the following steps:

  1. Click on Help
  2. Click on Driver Help
  3. Click on Siemens TCP/IP Ethernet
  4. Click on Device Setup
  5. Click on How to Configure S7-200 Connection in Micro/WIN
  6. Then after completing the Micro/WIN configuration, Click on S7 Communication Parameters

Important:  (Example) When your Micro/WIN TSAP is 10.00, you need to change the 10.00 hex to a decimal number (4096). (The 4096 decimal is 1000 hexadecimal.) And use the 4096 (decimal number) in the TSAP settings in the S7-200 Ethernet communication parameters.

The Siemens TCP/IP Ethernet Driver help file can also be found here.