Does the TOP Server GE Fanuc Suite Support PAC Systems PLCs?
We have a GE Fanuc PAC Systems PLC, and we were wondering if your TOP Server GE Fanuc Suite supports the PAC Systems PLCs?
As the GE Fanuc PAC Systems PLCs are mostly just like the 90/30 and 90/70 series, you can use the TOP Server GE Fanuc Suite and the GE Ethernet driver to communicate to the PAC PLCs. When configuring the driver, when you setup the device, pick GE OPEN as the device type.
However, there is one unsupported function: The driver will not support Bulk Memory, which is the "%W" memory type on the PAC Systems PLCs. As long as you do not need to use the "%W" memory type, the GE Ethernet driver with device type set to GE OPEN will work for you.