Connection to PLC with S5/S7 via USB-MPI
We cannot connect to our S7-300 with the S7 for Windows Software using the Siemens MPI/USB adapter cable. We have loaded the adapter software, but none of the settings we tried seem to work.
When you go to the preferences dialogue, use the following settings:
- Preferences from: = PC
- PLC Type = S7
- Protocol = SimaticNET
- SimaticNET: Click Select Connection.
- From the Interface Parameter Assignment select PC Adapter (MPI) and click OK.
- Make sure the MPI address, Rack Number (0 unless using a rack system) and CPU Slot are correct.
- Click OK.