You can read value even if the Object is not supported

Objects 13 and 42 don't appear to be supported, but I need to read these values.

Certain objects are not used in the driver because the values can be read from other objects.  If you need an object on the left side of the column you can read it by using the object on the right instead.

Object Name Use Object Name

2

Binary Input Change Event 1 Binary Input State
4 Double Bit Input Change Event 3 Double Bit Input State
11 Binary Output Change Event 10 Binary Output State
12 Control Relay Ouput Block 10 Binary Output State
13 Binary Output Command Event 10 Binary Output State
22 Counter Event Change 20 Counter Value
23 Frozen Counter Event Change 21 Frozen Counter Value
32 Analog Input change Event 30 Analog Input Value
41 Analog Output Write 40 Analog Output Value
42 Analog Output Change Event 40 Analog Output Value
43 Analog Output Command Event 40 Analog Output Value
51 Time and Date CTO 50 Time and Date
111 Octet String Event Change 110 Octet String Value