Wonderware SuiteLink Users - Wonderware Hotfix L00117361

Invensys Operations Management has brought to Software Toolbox's attention that Hotfix L00117361 has been released to address an issue introduced with the Wonderware Run Time Components (RTC) 3.0 SP2 update (June 2011).

A change was made to the wwsl.dll in that update to increase security by shrinking an internal buffer size.  This change introduced a problem for SuiteLink clients that may occur when a SuiteLink Client application is registering from a remote node or via terminal services (TSE) on the same node.

If you are experiencing issues in such a situation, it is recommended to apply this hotfix to resolve the issue.

Software Toolbox is providing this information and hotfix, with instructions, for your convenience, as Software Toolbox products such as TOP Server and OmniServer do provide a SuiteLink interface that could be affected by this issue.  This hotfix was provided by Invensys Operations Management and any questions or issues with this hotfix should be directed to your local Wonderware distributor.

 

Hotfix L00117361:
New WWSL.dll file version 59.23.2.1  2011-10-06
Replaces file version 58.9.0.0  2011-03-03

Installation Instructions:

  1. It is recommended to shutdown all the Wonderware applications that use the SuiteLink protocol prior to installation. Typically these will be:
    1. InTouch WindowViewer
    2. Wonderware DAServers
    3. Wonderware Historian
    4. Wonderware Application Server
    5. Any 3rd party SuiteLink capable products such as TOP Server or OmniServer
  2. Perform a backup of the WWSL.dll file from the "[RootDrive:]\Program Files\Common Files\ArchestrA" folder.
  3. If there is a Wonderware Application Server Platform deployed on the node, shutdown the platform the SMC Platform Manager. This is to stop all the engines that use SuiteLink Protocol.
  4. Go to "Control Panel->Administrative Tools->Services", and stop the "Wonderware SuiteLink" Service.
  5. Replace the WWSL.dll file in the "[RootDrive:]\Program Files\Common Files\ArchestrA" folder with file provided with the hot fix.
  6. Reboot the computer to apply the change and use the updated WWSL.DLL file. This will make sure that all of the Wonderware applications have successfully loaded the updated SuiteLink binaries.