Modbus addressing long/float in GE Multi UR Model T60 firmware 4.91
I have a GE Multi UR Model T60 firmware 4.91, all of my float values are correct. Why are all my long values coming in wrong?
In the GE Multi UR Model T60 device using firmware 4.91, long integers and memory floats are addressed this way:
- Long Integers -First word low in 32 bit data types.
- Memory Floats - First word high in 32 bit data types.
Create an identical channel and device in TOP Server and address the memory float tags using the first word high in 32 bit data types.