Connection Considerations with Triconex OPC A&E and DA Embedded Server (0x8007000e)

It is possible to connect to the embedded OPC A&E and DA Server.  However, there are a couple of considerations that must be made.

  1. This connection is still subject to DCOM permissions and local security policies.  See the recommended configuration settings at the following link:
    https://www.softwaretoolbox.com/dcom/
  2. It is important to confirm that you do not have any firewalls that are blocking communications between the OPC Client and Server.
  3. If you are receiving the error message 0x8007000e 'Not enough storage is available to complete this operation', confirm that you are not making any additional OPC Client connections as the number of concurrent connections may be limited.