Skip to content
  • There are no suggestions because the search field is empty.

Failed Reads/Writes using Honeywell UDC Driver

When using the TOP Server Honeywell UDC Driver, I am seeing failed reads and writes for Holding Registers.

When using the Honeywell 3000 UDC driver, it is necessary to set the block size to "1" when accessing holding registers because the Honeywell protocol uses variants instead of words. The same problem can also occur with other non-Modicon devices using the Modbus protocol.