TOP Server GE CCM Protocol Addressing

Can the TOP Server GE CCM driver use the same addressing as the GE Fanuc CCM2 I/O server from Wonderware version 7?

The current driver will now accept the Wonderware tag names without having to make the modifications below.

The outputs will be read only by default. The way they need to be addressed is below. Changes can be made quickly with a DB Dump and modification of the CSV file in Excel.

Device Address Range Data Type Access
Discrete I1 to I12288 Boolean Read Only Inputs
  I1 to I12281(every 8th bit) Byte, Word
  I1 to I12273(every 8th bit) Short, BCD
Discrete Q1 to Q12288 Boolean Read Only Outputs
  Q1 to Q12281 (every 8th bit) Byte, Word
  Q1 to Q12273 (every 8th bit) Short, BCD


The difference in addressing is not a method, but depends on what type of I/O address you are trying to communicate to in the Device. Extended I/O are different then regular I/O and can be written to and require the Hex O to F and + after the I or O and then the address offset number.